CATL EnerC+ 4.07 MWh / 0.5 P
Manufacturer | |
---|---|
Głębokość netto | |
Pojemność | |
Szerokość netto | |
Wysokość netto |
Product details
Manufacturer | |
---|---|
Głębokość netto | |
Pojemność | |
Szerokość netto | |
Wysokość netto |
CATL EnerC+ Containerized Energy Storage System (Model C02306P05L01)
Order lead time is 60/90 days
The CATL EnerC+ containerized energy storage system, model C02306P05L01, is an advanced solution designed for large-scale energy storage. Based on safe and efficient LiFePO4 (LFP) cells, this system offers a nominal energy capacity of 4073.47 kWh in a standard container configuration. It is a comprehensive solution built with a focus on high reliability, safety, and compliance with international standards and certifications.
Key features of the CATL EnerC+ Containerized Energy Storage System:
- High capacity and power: The system’s nominal energy is 4073.47 kWh with a nominal voltage of 1331.2 VDC. The nominal charge/discharge current is 1530A, and the nominal charge/discharge power is 2036.73 kW.
- Advanced LFP cell technology: Utilizes LiFePO4 cells with a capacity of 306Ah each, operating within a voltage range of 2.5-3.65V, ensuring high efficiency and safety.
- Comprehensive container design: Integrated within a standard container for easy land or sea transport and installation. Container dimensions are approximately 6058mm (width) x 2438mm (depth) x 2896mm (height).
- High level of safety and protection: IP55 protection rating for the battery bay and electrical compartment, and IP67 for the electrical control box of the cooling unit. The system meets numerous safety standards including UL1973, IEC62619, UL9540A.
- Wide operating range and environmental resistance: Operating temperature range from -25°C to +55°C, capable of functioning at altitudes up to 2000m without performance loss, and high corrosion resistance rating (C4, optional C5).
- Advanced communication and auxiliary power: Communication protocols include CAN, Modbus/TCP, with an integrated UPS (DC24V, 7Ah) to power BMS components.
Who is this the right choice for?
The CATL EnerC+ containerized energy storage system is an ideal solution for grid operators, developers of large-scale renewable energy projects, large industrial plants, and other entities requiring a reliable and efficient large-scale energy storage system. Its high capacity, advanced safety features, standards compliance, and comprehensive container design make it an excellent choice for grid stabilization, renewable energy integration, peak demand management, and backup power supply.
Parameter | Value | Remarks |
---|---|---|
Direct Current (DC) Data | ||
Product Model | C02306P05L01 | |
P-Rate | 0.5P | |
Cell | ||
Cell Type | LFP | |
Cell Capacity (Ah) | 306 | |
Cell Voltage Range (V) | 2.5-3.65 | Should not be lower than 2.5 V |
Rated Cell Energy (Wh) | 979.2 | |
System | ||
Configuration | 5P2P416S | |
Rated Energy (kWh) | 4073.47 | |
Rated Voltage (VDC) | 1331.2 | |
Voltage Range (VDC) | 1040~1500 | |
Rated Charging Current (A) | 1530 | |
Maximum Charging Current (A) | 1958.4 | For 1 minute |
Rated Charging Power (kW) | 2036.73 | |
Rated Discharging Current (A) | 1530 | |
Maximum Discharging Current (A) | 1958.4 | For 1 minute |
Rated Discharging Power (kW) | 2036.73 | |
Electrical Specifications – Auxiliary Power and Communication | ||
P-Rate | 0.5P | |
Auxiliary Power 1 | ||
Voltage Range | 3AC+N+PE 480V(380…480V) ±10%, 50/60Hz | For reference |
Power (kW) | Maximum 37.0 | |
Starting Current (A) | <67.5A, < 5s | |
Auxiliary Power 2 | ||
Voltage Range | 1AC230V(L+N) or 2AC480V(380…480V) | |
Power (kW) | Maximum 0.5kW (continuous) | |
Starting Current (A) | 5A | |
UPS | ||
Capacity | DC24V, 7Ah capacity @25°C | UPS is used only to power BMS components. The UPS is part of the auxiliary power supply. |
Communication Protocol | CAN, Modbus/TCP | |
Mechanical Specifications | ||
Transport | Land or sea transport | |
Dimensions (mm) | 2896mm (Height) * 2438mm (Depth) * 6058mm (Width) | |
Weight (t) | ~36.0t | |
Color | RAL7042 (Optional RAL 9003) | |
IP Rating | IP55 (Battery Room) IP55 (Electrical Room) IP67 (Electrical Control Box for cooling unit) |
|
Environmental Protection Specifications | ||
Charging Temperature Range (°C) | -25°C…+55 °C | CATL must be informed for professional assessment if temperature is outside this range |
Discharging Temperature Range (°C) | -25°C…+55 °C | |
Storage Temperature Range (°C) | -30°C…+60 °C | |
Operating Altitude (m) | <2000m (no derating of rated values) | |
Relative Humidity (%) | 0 ~ 95 % (non-condensing) | |
Battery Unit Corrosion Protection Level | C4, (optional C5) | |
Seismic Rating | IEEE 693-2018 Moderate Design Level | |
Certifications and Standards | ||
Cell: UN38.3 | UN transport testing for lithium batteries | |
Cell: UL1973 | Batteries for use in Light Electric Rail (LER) and stationary applications | |
Cell: IEC62619 | Safety requirements for secondary lithium cells and batteries for industrial applications | |
Cell: UL9540A | Energy Storage Systems and Equipment | |
Container: UL1973 | Batteries for use in Light Electric Rail (LER) and stationary applications | |
Container: NFPA855 | Standard for Stationary Energy Storage System Installations | |
Container: UL9540 | UL safety standard for Energy Storage Systems and Equipment | |
Container: UL9540A | Test method to evaluate fire propagation during uncontrolled temperature rise in battery energy storage systems | |
Container: IEC62477 Part 1 | Safety requirements for power electronic converter systems and equipment – General | |
Container: IEC62619 | Secondary cells and batteries containing alkaline or other non-acid electrolytes – Safety requirements for secondary lithium cells and batteries for industrial applications | |
Container: IEC 62933-5-2 | Electrical energy storage (EES) systems – Part 5-2: Safety requirements for grid-integrated EES systems based on electrochemistry | |
Container: IEC 61000-6-2 | Electromagnetic compatibility (EMC) – Part 6-2: Generic standards – Immunity standard for industrial environments | |
Container: IEC61000-6-4 | Electromagnetic compatibility (EMC) – Part 6-4: Generic standards – Emission standard for industrial environments |